7PG2113/4/5/6 Solkor Description of Operation
Figure 6.3-2 Logic Diagram: CT Supervision Function (60CTS) – 7PG2114/6
6.4
Broken Conductor (46BC)
The element calculates the ratio of NPS to PPS currents. Where the NPS:PPS current ratio is above
46BC
Setting
an output is given after the
46BC Delay
.
The Broken Conductor function can be inhibited from
Inhibit 46BC
A binary or virtual input.
Figure 6.4-1 Logic Diagram: Broken Conductor Function (46BC)
©2010 Siemens Protection Devices Limited Chapter 1 Page 74 of 80