![Siemens Solkor 7PG2113 Скачать руководство пользователя страница 59](http://html.mh-extra.com/html/siemens/solkor-7pg2113/solkor-7pg2113_technical-manual_382683059.webp)
7PG2113/4/5/6 Solkor Description of Operation
4.10 Voltage Protection: Neutral Overvoltage (59N) –
7PG2114/6
Two Neutral Overvoltage (or Neutral Voltage Displacement) elements are provided
59NIT & 59NDT
.
The relay utilises fundamental voltage measurement values for this function.
The 59NIT element can be configured to be either definite time lag (DTL) or inverse definite minimum time
(IDMT),
59NIT Setting
sets the pick-up voltage level (3V0) for the element.
An inverse definite minimum time (IDMT) can be selected using
59NIT Char
. A time multiplier is applied to the
characteristic curves using the
59NIT Time Mult
setting (M):
[ ]
ms
1
M
*
1000
t
Vs
3Vo
op
⎥
⎦
⎤
⎢
⎣
⎡
−
=
Alternatively, a definite time lag delay (DTL) can be chosen using
59NITChar
. When Delay (DTL) is selected the
time multiplier is not applied and the
59NIT Delay (DTL)
setting is used instead.
An instantaneous or definite time delayed reset can be applied using the
59NIT Reset
setting.
The 59NDT element has a DTL characteristic.
59NDT Setting
sets the pick-up voltage (3V0) and
59NDT Delay
the follower time delay.
Operation of the neutral overvoltage elements can be inhibited from:
Inhibit 59NIT
A binary or virtual input.
Inhibit59NDT
A binary or virtual input.
It should be noted that neutral voltage displacement can only be applied to VT arrangements that allow zero
sequence flux to flow in the core i.e. a 5-limb VT or 3 single phase VTs. The VT primary winding neutral must be
earthed to allow the flow of zero sequence current.
Figure 4.10-1
Logic Diagram: Neutral Overvoltage Element (59N)
©2010 Siemens Protection Devices Limited Chapter 1 Page 57 of 80