7PG2113/4/5/6 Solkor Description of Operation
Figure 2.5-4 LED Indication Label
2.6
Current Inputs
Four current inputs are provided on the Numeric module. Terminals are available for both 1A and 5A inputs.
The correct connections must be applied to suit the fixed 1A or 5A rating of the Solkor R/Rf module.
Current is sampled at 1600Hz for both 50Hz and 60Hz system frequencies. Protection and monitoring functions of
the relay use either the Fundamental Frequency RMS or the True RMS value of current appropriate to the
individual function.
The waveform recorder samples and displays current input waveforms at 1600Hz.
2.7
Voltage Inputs
Three voltage inputs are provided on the Analogue Input module of the 7PG2114/6 relays.
Voltage is sampled at 1600Hz for both 50Hz and 60Hz system frequencies. Protection and monitoring functions of
the relay use fundamental frequency voltage measurement.
The waveform recorder samples and displays voltage input waveforms at 1600Hz.
©2010 Siemens Protection Devices Limited Chapter 1 Page 21 of 80