Section 3: IEC 60870-5-103 Definitions
3.1
Introduction
This section describes the IEC 60870-5-103 protocol implementation in the relays. This protocol is used for the
communication with Reydisp software and can also be used for communication with a suitable control system.
The control system or local PC acts as the master in the system with the relay operating as a slave responding to
the master’s commands. The implementation provides event information, time synchronising, commands and
measurands and also supports the transfer of disturbance records.
This protocol can be set to use any or all of the relays hardware interfaces and is the standard protocol used by
the USB port. The relay can communicate simultaneously on all ports regardless of protocol used.
Each relay must be given an address to enable communication and can be set by the
Communication
Interface:Relay Address.
A relay with the default address of
0
will not be able to communicate.
Cause of Transmission
The cause of transmission (COT) column of the ‘Information Number and Function’ table lists possible causes of
transmission for these frames. The following abbreviations are used:
Abbreviation Description
SE spontaneous
event
T test
mode
GI general
interrogation
Loc local
operation
Rem remote
operation
Ack command
acknowledge
Nak
Negative command acknowledge
Note: Events listing a GI cause of transmission can be raised and cleared; other events are raised only.
Function Type
Abbreviation Description
1
Time tagged message (monitor direction)
2
Time tagged message (relative time) (monitor direction)
3.1 Measurands
I
4
Time-tagged measurands with relative time
5 Identification
message
6 Time
synchronisation
7
General Interrogation Initialization
9 Measurands
II
20 General
command
Information Number and Function
The following table lists information number and function definitions together with a description of the message
and function type and cause of transmission that can result in that message. The table shows all events available
from the relay range.