![Siemens SIWAREX WP251 Скачать руководство пользователя страница 79](http://html.mh-extra.com/html/siemens/siwarex-wp251/siwarex-wp251_manual_374538079.webp)
Scale parameters and functions
8.5 DR 4 Output of calculated calibration digits
SIWAREX WP251
Manual, 12/2015, A5E37203357A
79
The load cell parameters must subsequently be defined in data record 10. Command 82
"Perform automatic calibration" then uses this data and the currently applied dead load to
calculate the characteristic curve of the scale. The characteristic curve is active immediately.
Note
The characteristic curve data in data record 3 active prior to execution of command 82 is
directly overwritten.
Automatic calibration requires the following criteria:
●
Correct mechanical installation of the scale
●
Scale is empty (only mechanical installation (= dead load) present on the cells)
●
Installed load cells are evenly loaded
●
There are no shunt circuits
8.5
DR 4 Output of calculated calibration digits
8.5.1
Overview
Data record DR 4 outputs the digits calculated from the automatic scale calibration and the
calibration check. This data record cannot be sent to the scales.
Table 8- 2
Assignment of data record 4
Variable
Note
Type
Length
(bytes)
Rw
Default
Min.
Max.
Modbus
Register
Data record
number
Contains no. of
the data record
USHORT
2
r
4
-
-
1200
Length
Data record length
information
USHORT
2
r
28
-
-
1201
Application
Information about
which application
the DR belongs to
USHORT
2
r
105
-
-
1202
Version identifi-
er
Current data rec-
ord version infor-
mation
USHORT
2
r
1
1
65635
1203
(Page 80)
Calibration digits 0
(calculated):
calibration digits
calculated by
'automatic calibra-
tion'
LONG
4
r
200000
0
1600000
1204
Содержание SIWAREX WP251
Страница 28: ...Mounting 5 3 Mounting on the SIMATIC S7 1200 SIWAREX WP251 28 Manual 12 2015 A5E37203357A ...
Страница 40: ...Connection 6 12 Attachment of calibration protection plate SIWAREX WP251 40 Manual 12 2015 A5E37203357A ...
Страница 56: ...Commissioning 7 5 Service with the SIWATOOL program SIWAREX WP251 56 Manual 12 2015 A5E37203357A ...
Страница 162: ...Scale parameters and functions 8 38 DR 48 date and time 2 for Modbus SIWAREX WP251 162 Manual 12 2015 A5E37203357A ...
Страница 212: ...Technical specifications 13 3 Approvals SIWAREX WP251 212 Manual 12 2015 A5E37203357A ...