![Siemens SIWAREX WP251 Скачать руководство пользователя страница 78](http://html.mh-extra.com/html/siemens/siwarex-wp251/siwarex-wp251_manual_374538078.webp)
Scale parameters and functions
8.4 Calibration
SIWAREX WP251
78
Manual, 12/2015, A5E37203357A
Image 8-4
Linearizing the scales' characteristic curve
Load
Comment
Load
Digits
L=0
100 kg load cell (2 mV/V) not
loaded
Approx. 0
L0
Mechanical installation on load
cell (dead load)
e.g. 25 kg
Approx. 500 000
L1
Calibration weight 1 placed
onto scale
e.g. 60 kg
Approx. 1 200 000
L2
Calibration weight 2 placed
onto scale
e.g. 80 kg
Approx. 1 650 000
L
max
Nominal weight of load cell
100 kg
Approx. 2 000 000
L
max
+10 %
Rated approx. 10 %
Approx. 110 kg
Approx. 2 200 000
8.4.2
Automatic calibration
Scales can be rapidly commissioned with automatic calibration. The accuracy of the scale
greatly depends on the entered parameters and the mechanical properties of the scale. The
best level of accuracy for the scale can be achieved by calibrating with calibration weights.
During initial commissioning with automatic calibration, the module must be reset using the
"Load factory settings" or "Load standard parameters" command.
Содержание SIWAREX WP251
Страница 28: ...Mounting 5 3 Mounting on the SIMATIC S7 1200 SIWAREX WP251 28 Manual 12 2015 A5E37203357A ...
Страница 40: ...Connection 6 12 Attachment of calibration protection plate SIWAREX WP251 40 Manual 12 2015 A5E37203357A ...
Страница 56: ...Commissioning 7 5 Service with the SIWATOOL program SIWAREX WP251 56 Manual 12 2015 A5E37203357A ...
Страница 162: ...Scale parameters and functions 8 38 DR 48 date and time 2 for Modbus SIWAREX WP251 162 Manual 12 2015 A5E37203357A ...
Страница 212: ...Technical specifications 13 3 Approvals SIWAREX WP251 212 Manual 12 2015 A5E37203357A ...
Страница 218: ...List of abbreviations B 1 List of abbreviations SIWAREX WP251 218 Manual 12 2015 A5E37203357A ...