Weighing Functions
SIWAREX FTA
5-73
Name
Type
Address Default
Range of Values / Explanation
Reference
S7-Interface
0
Reserve
BYTE
DBB000
0
Source for the weight
simulation
BYTE
DBB001
0
0: Weight simulation inactive
1: Weight simulation value of SIMATIC
2: Weight simulation value of RS232
Other definitions not permitted.
Decade used for
rounding the decimal
places of the process
values
(Float weight values)
BYTE
DBB002
3
0: Round to 0 decimal places
1: Round to 1 decimal place
2: Round to 2 decimal places
3: Round to 3 decimal places
4: Round to 4 decimal places
5: Round to 5 decimal places
6: Round to 6 decimal places
Reserve
BYTE
DBB003
0
Reserve
Force service operation
BYTE
DBB004
0
Bit 0 :
0: Outputs in service operation - Forced
operation not possible
1: Outputs in service operation - Forced
operation possible
Bit 1 - 7 not used
Process value 1 for fast
output to the SIMATIC
CPU
BYTE
DBB005
1
Various process values are available for
selection after listing.
Process value 2 for fast
output to the SIMATIC
CPU
BYTE
DBB006
2
Various process values are available for
selection after listing.
Reserve 2
BYTE
DBB007
0
Reserve 2
S7-Alarm
Definition of process
alarm 0
WORD
DBB008
0
Value 0 - No process alarm generation
Value range 1 – 0FFh
Number of the technical error
Value range 100h – 13Fh
100h+ 0...1Fh Bit-No. NAWI-status bit - coming
100h+ 20h...3Fh Bit-No. AWI Status flag - coming
Value range 200h – 23Fh
200h+ 0...1Fh Bit-No. NAWI status bit - going
200h+ 20h...3Fh Bit-No. AWI status bit - going
Definition of process
alarm 1
WORD
DBB010
0
Value 0 - No process alarm generation
Value range 1 – 0FFh
Number of the technical error
Value range 100h – 13Fh
100h+ 0...1Fh Bit-No. NAWI-status bit - coming
100h+ 20h...3Fh Bit-No. AWI Status bit - coming
Value range 200h – 23Fh
200h+ 0...1Fh Bit-No. NAWI status bit - going
200h+ 20h...3Fh Bit-No. AWI status bit - going
Definition of process
alarm 2
WORD
DBB012
0
Value 0 - No process alarm generation
Value range 1 – 0FFh
Number of the technical error
Value range 100h – 13Fh
100h+ 0...1Fh Bit-No. NAWI-status bit - coming