Weighing Functions
SIWAREX FTA
5-101
5.16.6 DR 23 - Default value for analog output with course
If the output of a fixed value has been defined during the coarse-/fine-signal
) then the output current during the coarse
signal is defined with the parameter (1... 100%).
5.16.7 DR 23 - Default value for analog output with fine
If the output of a fixed value has been defined during the coarse-/fine-signal
) then the output current during the fine
signal is defined with the parameter (1... 100%).
5.16.8 DR 23 - Filter type for dosing
A separate low-pass filter is used exclusively for the precise control of switching
the coarse and fine signal off. Normally, these settings should correspond with the
settings for the filter in DR3.
The filter type can be defined with this parameter.
5.16.9 DR 23 - Depth of the mean value filter for dosing
A separate mean value filter is used exclusively for the precise control of switching
the coarse and fine signal off.
The mean value filter is used to calm the weight value when there is incidental
interference. The weight value is based on the average of the n weight values that
the SIWAREX FTA calculates every 10 msec, e.g. if n=10, 10 values are used to
calculate the average value. Every 10 msec, the oldest value is removed and the
newest is taken into account in the calculation.
5.16.10 DR 23 - Limit Frequency Filter for dosing
A separate low-pass filter is used exclusively for the precise control of switching
the coarse and fine signal off. Normally, these settings should correspond with the
settings for the filter in DR3.
The limit frequency of the low-pass filter can be defined with this parameter.
5.16.11 DR 23 - Tare-/Zero setting mode
This parameter defines whether the scale starts with:
o
neither taring nor zero setting,
o
zero setting,
o
taring,
o
taring with a tare average value (from 10 taring procedures),
o
or the external tare definition (see