Connection
3.2 Terminal connections to Siemens Integrators
SITRANS WS100
14
Operating Instructions, 06/2011, 7ML19985LU02-00
Wiring
Note
Ground the cable shield at the integrator end only!
For optimal performance the stainless steel cover of the Speed Sensor must be
connected to a reliable earthed ground.
WS100 Standard:
●
Red: +V DC (the positive power supply from the integrator connection).
●
White: Speed Out (the positive output connection of the measurement loop).
●
Black: Common (the common connection used as a reference point with the integrator).
●
GND: Ground (a ground connection). Do not use this ground for the cable shield.
WS100 IS
●
Brown: +V DC (the positive power supply from the integrator connection).
●
Blue: Speed Out (the positive output connection of the measurement loop).
●
GND: Ground (a ground connection). Do not use this ground for the cable shield.
3.2
Terminal connections to Siemens Integrators
Terminal connections to Siemens Integrators
SITRANS WS100 Red
+V DC
White
Speed
Black
COM
GND
Milltronics BW100 8
7
6
N/C
Milltronics BW500 19
16
17
N/C
SIWAREX FTC
24 V
(backplane bus)
X1.9
(CI+)
X1:10
(CI-)
N/C