Technical data
10.7 Option modules
SITRANS VP300 with or without HART
160
Operating Instructions, 03/2011, A5E01258666-03
Explosion protection
Ex markings
Explosion protection in accordance with ATEX/IECEx
FM/CSA
Installation point
Intrinsic safety "ia"
Zones 1, 21, 22
Types of protection "ic", "nA"
Zone 2
Protection by enclosure "tb"
Zones 21, 22
Permissible ambient temperature
1)
T4: -40 ... +80 °C (-40 ... +176 °F)
T6: -40 ... +50 °C (-40 ... +122 °F)
1)
At ≤ -20 °C (-4 °F), the refresh rate of the display is limited. At > 70 °C (158 °F), the contrast of the display is limited.
10.7
Option modules
Option modules
Without explosion protection
With explosion protection Ex "ia", "ic",
"nA"
Explosion protection in accordance with
ATEX/IECEx
-
"ia"/"ic": Zone 1: II 2 G Ex ia IIC
Zone 2: II 3 G Ex ic IIC
Zones 21, 22: II 2 D Ex ia IIIC
"nA": Zone 2: II 3 G Ex nA IIC
Installation point
-
Zones 1, 2, 21, 22
Permissible ambient temperature for
operation taking self-heating into
account
-40 ... +90 °C
(-40 ... +194 °F)
-40 ... +90 °C
(-40 ... +194 °F)
Note: The device dust explosion protection by enclosure "tb" automatically results for option
modules through the installation in the positioner enclosure. Take account of the maximum
values for the connection.
Содержание SITRANS VP300
Страница 2: ......
Страница 130: ...Operate 6 2 Parameter description SITRANS VP300 with or without HART 128 Operating Instructions 03 2011 A5E01258666 03 ...
Страница 184: ...Glossary SITRANS VP300 with or without HART 182 Operating Instructions 03 2011 A5E01258666 03 ...
Страница 188: ...Index SITRANS VP300 with or without HART 186 Operating Instructions 03 2011 A5E01258666 03 ...
Страница 189: ......