SITRANS TR200/TR300
Operating Instructions, 06/2010, A5E01071992-03
41
Commissioning
8
8.1
Commissioning
WARNING
Missing type of protection
If the transmitter is not operated with an intrinsically-safe power supply, the type of
protection "Intrinsic safety" is no longer guaranteed and the intrinsically-safe approval may
be revoked.
Permanently erase, therefore, the irrelevant types of protection on the nameplate before
commissioning to ensure that erroneous deployment is avoided.
Procedure
1.
Program the transmitter's operating data according to the actual requirements.
If applicable, enter the changed operating data on the additional plate on the enclosure.
2.
Assemble the transmitter.
3.
Connect the sensor to the power supply, see Chapter Connecting (Page 21).
4.
Turn on the auxiliary power supply.
5.
Wait about 10 seconds. After this start-up time the transmitter is operational.
Note
Warming-up
To obtain exact measured values, the transmitter needs to be allowed to warm up for five
minutes or so after the power supply has been switched on.
8.2
LED operating indicator
● Operating indicator does not light: No supply voltage
● Constant green light: Everything OK, normal error-free operating state
● Constant/flashing red light: Disrupted operation
– Flashing (ca. 2 Hz) red light: Indication of faults independent of the device, e.g. wire
break, sensor short circuit, violation of sensor limits
– Constant red light: Indication of errors in the device, e.g. RAM-,
ROM-, EEPROM-, CHECKSUM-, WATCHDOG-, STACK error or violation of the
permitted ambient temperature limits and if the minimum supply voltage for the device
is not reached.
Содержание sitrans tr300
Страница 7: ...Table of contents SITRANS TR200 TR300 6 Operating Instructions 06 2010 A5E01071992 03 ...
Страница 13: ...General safety notes 2 5 Measures SITRANS TR200 TR300 12 Operating Instructions 06 2010 A5E01071992 03 ...
Страница 21: ...Installation SITRANS TR200 TR300 20 Operating Instructions 06 2010 A5E01071992 03 ...
Страница 43: ...Commissioning 8 2 LED operating indicator SITRANS TR200 TR300 42 Operating Instructions 06 2010 A5E01071992 03 ...
Страница 69: ...Service and maintenance SITRANS TR200 TR300 68 Operating Instructions 06 2010 A5E01071992 03 ...
Страница 81: ...Dimension drawings SITRANS TR200 TR300 80 Operating Instructions 06 2010 A5E01071992 03 ...
Страница 83: ...Spare parts and accessories SITRANS TR200 TR300 82 Operating Instructions 06 2010 A5E01071992 03 ...
Страница 87: ...List of abbreviations B 1 Abbreviations SITRANS TR200 TR300 86 Operating Instructions 06 2010 A5E01071992 03 ...
Страница 93: ...Glossary SITRANS TR200 TR300 92 Operating Instructions 06 2010 A5E01071992 03 ...