Connecting
5.1 Safety notes on connection
SITRANS TR200/TR300
22
Operating Instructions, 06/2010, A5E01071992-03
5.1.2
Safety notes when connecting in hazardous areas
WARNING
Observe the degree of protection
The device must be connected to the supply and signal circuits named in the certificate or
on the nameplate.
When installing the device in hazardous areas:
Use enclosures/connection heads with the degree of protection corresponding to the test
certificate applicable in your country.
WARNING
Electrical connection in hazardous areas
The national directives and laws for hazardous areas valid in your country must be
observed for electrical connection. In Germany these are, for example:
The health and safety at work regulations
The directive for "Installation of electrical systems in hazardous areas", DIN EN 60079-
14 (previously VDE 0165,T1)
The EC type examination certificate
When a auxiliary power supply is needed, check whether the auxiliary power supply
matches that given on the nameplate and with the inspection certificate valid in your
country.
CAUTION
Limited range of use
If the device has been operated outside the ambient conditions specified for potentially
explosive atmospheres, you may no longer operate the device in potentially explosive
atmospheres. Make sure to permanently mask all Ex markings on the nameplate.
NOTICE
Loss of type of protection "Intrinsic safety"
If the transmitter is not operated with an intrinsically-safe power supply, the type of
protection "Intrinsic safety" is no longer guaranteed and the intrinsically-safe approval may
be revoked.
Permanently erase, therefore, the irrelevant types of protection on the nameplate before
commissioning to ensure that erroneous deployment is avoided.
4 to 20 mA input and sensor circuits are galvanically isolated and tested with a test voltage
of 2.12 kVDC/1 minute.
The sensor circuit is reliably galvanically isolated from the auxiliary power supply and signal
circuit, up to a peak value of the rated voltage of 60 V. Be sure to observe the construction
directives valid at the construction location for electrical resources in hazardous areas. In
Europe, this is the standard EN 60079-14.
Содержание sitrans tr300
Страница 7: ...Table of contents SITRANS TR200 TR300 6 Operating Instructions 06 2010 A5E01071992 03 ...
Страница 13: ...General safety notes 2 5 Measures SITRANS TR200 TR300 12 Operating Instructions 06 2010 A5E01071992 03 ...
Страница 21: ...Installation SITRANS TR200 TR300 20 Operating Instructions 06 2010 A5E01071992 03 ...
Страница 43: ...Commissioning 8 2 LED operating indicator SITRANS TR200 TR300 42 Operating Instructions 06 2010 A5E01071992 03 ...
Страница 69: ...Service and maintenance SITRANS TR200 TR300 68 Operating Instructions 06 2010 A5E01071992 03 ...
Страница 81: ...Dimension drawings SITRANS TR200 TR300 80 Operating Instructions 06 2010 A5E01071992 03 ...
Страница 83: ...Spare parts and accessories SITRANS TR200 TR300 82 Operating Instructions 06 2010 A5E01071992 03 ...
Страница 87: ...List of abbreviations B 1 Abbreviations SITRANS TR200 TR300 86 Operating Instructions 06 2010 A5E01071992 03 ...
Страница 93: ...Glossary SITRANS TR200 TR300 92 Operating Instructions 06 2010 A5E01071992 03 ...