Operate
6.2 Parameter description
SITRANS P500 with HART
70
Operating Instructions, 12/2014, A5E02344528-09
Purpose:
Setting the start of scale value (MA)
Description:
This parameter allows you to set the MA. By inputting the pressure MA and
pressure ME, a rising characteristic results if MA < ME. A decreasing char-
acteristic results if MA > ME.
Combinations that result in a range that is smaller than the smallest permis-
sible range (depending on the measuring cell) will be rejected.
"1.1.3.1.3 Setting URV"
Factory setting:
Upper measurement limit, or as specified in order
Setting range:
Sensor limits
Purpose:
Setting the full scale value (ME)
Description:
This parameter allows you to set the full scale value. By inputting the pres-
sure MA and pressure ME a rising characteristic results if MA < ME. If
MA > ME, this results in a falling characteristic.
Combinations that result in a range that is smaller than the smallest permis-
sible range (depending on the measuring cell) will be rejected.
"1.1.3.2 With Pressure"
"1.1.3.2.1 Pressure Unit"
Factory setting:
mbar
Setting range:
inH
2
O, inHg, ftH
2
O, mmH
2
O, mmHg, psi, bar, mbar, g/cm
2
, kg/cm
2
, Pa, kPa,
HPa, Torr, atm, MPa, inH
2
O (4 °C), mmH
2
O (4 °C)
Purpose:
Selection of the unit for the pressure parameter
Description:
This parameter allows you to select the unit for the measured pressure
value. The parameters associated with this unit are automatically converted
to the new unit.
"1.1.3.2.2 Set LRV with Pressure"
Setting range:
Within sensor limits
Purpose:
Setting the start of scale value
Description:
Use this parameter to set the start of scale value to the current pressure
value. The change to the start of scale value causes a respective change to
the full scale value, so that the range remains constant. Should the move-
ment of the full scale value violate an upper or lower sensor limit, setting of
the start of scale value is rejected.
Содержание SITRANS P500
Страница 1: ......
Страница 2: ......
Страница 10: ...Table of contents SITRANS P500 with HART 10 Operating Instructions 12 2014 A5E02344528 09 ...
Страница 14: ...Introduction 1 6 Notes on warranty SITRANS P500 with HART 14 Operating Instructions 12 2014 A5E02344528 09 ...
Страница 214: ...Technical data 11 9 HART communication SITRANS P500 with HART 214 Operating Instructions 12 2014 A5E02344528 09 ...
Страница 218: ...Dimension drawings 12 2 Level SITRANS P500 with HART 218 Operating Instructions 12 2014 A5E02344528 09 ...
Страница 221: ...Appendix A 3 Overview SITRANS P500 with HART Operating Instructions 12 2014 A5E02344528 09 221 Continued on next page ...
Страница 222: ...Appendix A 3 Overview SITRANS P500 with HART 222 Operating Instructions 12 2014 A5E02344528 09 Continued on next page ...
Страница 223: ...Appendix A 3 Overview SITRANS P500 with HART Operating Instructions 12 2014 A5E02344528 09 223 Continued on next page ...
Страница 224: ...Appendix A 3 Overview SITRANS P500 with HART 224 Operating Instructions 12 2014 A5E02344528 09 Continued on next page ...
Страница 225: ...Appendix A 3 Overview SITRANS P500 with HART Operating Instructions 12 2014 A5E02344528 09 225 Continued on next page ...
Страница 226: ...Appendix A 3 Overview SITRANS P500 with HART 226 Operating Instructions 12 2014 A5E02344528 09 ...
Страница 228: ...Appendix A 4 Technical support SITRANS P500 with HART 228 Operating Instructions 12 2014 A5E02344528 09 ...
Страница 230: ...List of abbreviations SITRANS P500 with HART 230 Operating Instructions 12 2014 A5E02344528 09 ...
Страница 234: ...Glossary SITRANS P500 with HART 234 Operating Instructions 12 2014 A5E02344528 09 TP Total Performance ...
Страница 238: ......