
See also
10.1.4
Operating modes of the device
The device can be operated as follows:
● "Functional Safety disabled" is used for operation in non-safety-related applications.
● "Functional Safety enabled" is used for operation in safety-related applications.
See also
Enabling Functional Safety (Page 160)
10.1.5
Device mode
When Functional Safety is disabled, the following device modes are displayed via the display
or remote operation:
Device mode
Description
Current output value
Safe current output
Functional Safety disa‐
bled
Used for operation in
non-safety-related ap‐
plications.
The safety-related pa‐
rameters of the device
are set.
Operating signal
(4 to 20 mA)
No
The safety-relevant pa‐
rameters and the fail-
safe behavior are vali‐
dated.
Out of service, non-safe
mode
The device is out of
service (e.g. a firmware
update is running)
Failure signal
(≤ 3.6 mA or ≥ 21 mA)
No
Functional Safety
10.1 Safety concept
SITRANS P320/P420 (mA/HART)
Operating Instructions, 06/2018, A5E44852162-AA
157
Содержание SITRANS P320
Страница 10: ...Table of contents SITRANS P320 P420 mA HART 10 Operating Instructions 06 2018 A5E44852162 AA ...
Страница 18: ...Introduction 2 7 Notes on warranty SITRANS P320 P420 mA HART 18 Operating Instructions 06 2018 A5E44852162 AA ...
Страница 174: ...Functional Safety 10 7 Repair and service SITRANS P320 P420 mA HART 174 Operating Instructions 06 2018 A5E44852162 AA ...
Страница 260: ...Index SITRANS P320 P420 mA HART 260 Operating Instructions 06 2018 A5E44852162 AA ...