9.2.33
Reset [35]
Used to reset the following settings:
Setting range:
Restore ordered configuration
CUST
Reset to sensor calibration
SENSR
Reset DAC trim to the factory setting
DAC
Factory reset
FACT
9.2.33.1
Reset to sensor calibration
Resets the zero point adjustment and sensor calibration to the factory setting.
9.2.33.2
Reset DAC trim to the factory setting
Resets the DAC trim (digital-to-analog converter trim) to the factory setting.
The DAC trim is used to calibrate the 4 mA and 20 mA end points of the analog output with
an external reference (e.g. current measurement device).
The DAC trim is available over remote operation.
Parameter assignment
9.2 Parameter assignment over device with display
SITRANS P320/P420 (mA/HART)
140
Operating Instructions, 06/2018, A5E44852162-AA