Installation
4.3 Installation for level version
SITRANS P300 with HART communication
4-6
Operating Instructions, 06/2005, A5E00359579-02
Installation height
0(
0$
S
R
K
X
K
Level of open container
Formula:
Zero point: p
MA =
ρ · g · H
U
Zero point: p
ME =
ρ · g · H
O
MA
Zero point
Δp
MA
Limit point to be adjusted
ME
Limit point
Δp
ME
Limit point to be adjusted
p
Pressure
ρ
Density of the measured medium in the container
h
U
Zero point
g
Local gravitational acceleration
h
O
Limit point
Note
Select the height of the container flange for recording of the transmitter (
measuring point)
such that the lowest level to be measured is always over the flange or at its upper edge.
4.3.2
Installation for level
Note
Seals are required for the installation.
Seals are not included in the delivery.