B.1.3
Deactivate buffers when connecting via serial modem
Introduction
This deactivation is required to align SIMATIC PDM with the HART modem when using a
Microsoft Windows operating systems.
Deactivating buffers is not necessary when connecting via USB.
Condition
● You connect via RS232 (COM1).
● You have administrative rights on your operating system.
● You know the hardware and software requirements SIMATIC PDM installation
documentation.
Procedure
1. Check the Operating Instructions for SIMATIC PDM for hardware and software
requirements.
2. From the computer desktop, click "Start > Control Panel" to begin configuration.
3. Click "System and Security".
4. Select "Device Manager" under "System".
5. Open folder "Ports".
6. Double click the COM Port used by the system to open the properties window.
7. Select the tab "Port Settings".
8. Click the "Advanced" button.
If the "Use FIFO buffers" radio box is selected, click to deselect.
①
Deselect "Use FIFO buffers" radio box
9. Click "OK" button to close out.
10.Close all screens.
11.Restart the computer.
Remote operation
B.1 SIMATIC PDM
SITRANS P320/P420 with 4 to 20 mA/HART
260
Operating Instructions, 11/2019, A5E44852162-AC