13.1.7
Differential pressure and flow
Differential pressure input and flow
Measured variable
Differential pressure and flow
Measuring span (continuous‐
ly adjustable) and maximum
operating pressure (accord‐
ing to 2014/68/EU Pressure
Equipment Directive)
Measuring span
1)
Maximum permissible
operating pressure
MAWP (PS)
Max. permissible
test pressure
1 ... 20 mbar
0.1 ... 2 kPa
0.4015 … 8.031 inH
2
O
160 bar
16 MPa
2320 psi
240 bar
24 MPa
3480 psi
1 ... 60 mbar
0.1 ... 6 kPa
0.4015 … 24.09 inH
2
O
160 bar
16 MPa
2320 psi
240 bar
24 MPa
3480 psi
2.5 ... 250 mbar
0.2 ... 25 kPa
1.004 … 100.4 inH
2
O
160 bar
16 MPa
2320 psi
240 bar
24 MPa
3480 psi
6 ... 600 mbar
0.6 ... 60 kPa
2.409 … 240.9 inH
2
O
160 bar
16 MPa
2320 psi
240 bar
24 MPa
3480 psi
16 ... 1600 mbar
1.6 ... 160 kPa
6.424 … 642.4 inH
2
O
160 bar
16 MPa
2320 psi
240 bar
24 MPa
3480 psi
50 ... 5000 mbar
5 ... 500 kPa
20.08 … 2008 inH
2
O
160 bar
16 MPa
2320 psi
240 bar
24 MPa
3480 psi
0.3 … 30 bar
0.03 ... 3 MPa
4.35 … 435 psi
160 bar
16 MPa
2320 psi
240 bar
24 MPa
3480 psi
2.5 ... 250 mbar
0.25 ... 25 kPa
1.004 … 100.4 inH
2
O
420 bar
42 MPa
6091 psi
630 bar
63 MPa
9137 psi
6 ... 600 mbar
0.6 ... 60 kPa
2.409 … 240.9 inH
2
O
420 bar
42 MPa
6091 psi
630 bar
63 MPa
9137 psi
16 ... 1600 mbar
1.6 ... 160 kPa
6.424 … 642.4 inH
2
O
420 bar
42 MPa
6091 psi
630 bar
63 MPa
9137 psi
50 ... 5000 mbar
5 ... 500 kPa
20.08 … 2008 inH
2
O
420 bar
42 MPa
6091 psi
630 bar
63 MPa
9137 psi
0.3 … 30 bar
0.03 ... 3 MPa
4.35 … 435 psi
420 bar
42 MPa
6091 psi
630 bar
63 MPa
9137 psi
Technical data
13.1 Input
SITRANS P320/P420 with 4 to 20 mA/HART
206
Operating Instructions, 11/2019, A5E44852162-AC
Содержание SITRANS P
Страница 10: ...Table of contents SITRANS P320 P420 with 4 to 20 mA HART 10 Operating Instructions 11 2019 A5E44852162 AC ...
Страница 272: ...Abbreviations SITRANS P320 P420 with 4 to 20 mA HART 272 Operating Instructions 11 2019 A5E44852162 AC ...
Страница 280: ...Index SITRANS P320 P420 with 4 to 20 mA HART 280 Operating Instructions 11 2019 A5E44852162 AC ...