3.8 mA
22.8 mA
20 mA
20.5 mA
4 mA
3.55 mA
①
Normal operation
②
Lower fault current (factory setting)
③
Lower saturation limit (factory setting)
④
Upper saturation limit (factory setting)
⑤
Upper fault current (factory setting)
9.2.12
Upper saturation limit [14]
Sets the threshold for the upper saturation limit
④
.
Setting range:
Between 20 mA and the upper fault current
Factory setting:
20.5 mA, or as specified in order
3.8 mA
22.8 mA
20 mA
20.5 mA
4 mA
3.55 mA
①
Normal operation
②
Lower fault current (factory setting)
③
Lower saturation limit (factory setting)
④
Upper saturation limit (factory setting)
⑤
Upper fault current (factory setting)
Parameter assignment
9.2 Parameter assignment over device with display
SITRANS P320/P420 with 4 to 20 mA/HART
126
Operating Instructions, 11/2019, A5E44852162-AC