SITRANS LR200 with mA/HART
Operating Instructions, 05/2019, A5E32337676-AE
99
7.2.1
Sensor (2.2.)
7.2.1.1
Units (2.2.1.)
Description
sensor measurement units
Options
m, cm, mm, ft, in
Factory setting
m
7.2.1.2
Sensor mode (2.2.2.)
①
Sensor value
⑤
Low calibration point
②
Space
⑥
Far range
③
Distance
⑦
Level
④
High calibration point
Mode
Description
Reference point
NO SERVICE
Measurement and associated loop
current are not updated, and the
device defaults to Fail-safe mode
1)
.
N/A
LEVEL
(factory setting)
Distance to material surface
Low Calibration Point (process empty
level)
SPACE
High Calibration Point (process full level)
DISTANCE
Sensor Reference Point
1)
For more detail, refer to Material level (2.5.1.) (Page 103).
7.2.1.3
Material (2.2.3.)
Description
Automatically configures the device to operate in the chosen application type, by
changing one or more of the following parameters: Propagation Factor, Position
Detect, and/or CLEF Range.
Options
LIQUID
LIQUID LOW DK
1)
(low dielectric liquid - CLEF algorithm enabled
Factory setting LIQUID
Related
parameters
Propagation factor (2.8.3.) (Page 111)
Position detect (2.8.4.2.) (Page 112)
CLEF range (2.8.4.4.) (Page 112)
1)
dK < 3.0
Содержание SITRANS LR200 7ML5422
Страница 185: ...SITRANS LR200 with mA HART Operating Instructions 05 2019 A5E32337676 AE 185 B 5 4 PFTE rod antenna threaded connection ...
Страница 193: ...SITRANS LR200 with mA HART Operating Instructions 05 2019 A5E32337676 AE 193 ...
Страница 194: ...SITRANS LR200 with mA HART 194 Operating Instructions 05 2019 A5E32337676 AE ...
Страница 212: ...Index SITRANS LR200 with mA HART 212 Operating Instructions 05 2019 A5E32337676 AE ...