![Siemens SITRANS LR200 7ML5422 Скачать руководство пользователя страница 30](http://html.mh-extra.com/html/siemens/sitrans-lr200-7ml5422/sitrans-lr200-7ml5422_operating-instructions-manual_384663030.webp)
SITRANS LR200 with mA/HART
30
Operating Instructions, 05/2019, A5E32337676-AE
WARNING
Unprotected cable ends
Risk of explosion through unprotected cable ends in hazardous areas.
•
Protect unused cable ends in accordance with IEC/EN 60079-14.
WARNING
Improper laying of shielded cables
Risk of explosion through compensating currents between hazardous area and the
non-hazardous area.
•
Shielded cables that cross into hazardous areas should be grounded only at one end.
•
If grounding is required at both ends, use an equipotential bonding conductor.
Note
Electromagnetic compatibility (EMC)
For metal housings there is an increased electromagnetic compatibility compared to high-
frequency radiation. This protection can be increased by grounding the housing, see
Connecting (Page 29).
5.2
Connecting SITRANS LR200
Note
•
Check the nameplate on your instrument, to verify the approval rating.
•
Use appropriate conduit seals to maintain IP or NEMA rating.
•
See Nameplates for hazardous area installations (Page 33).
•
Use a twisted pair cable: AWG 22 to 14 (0.34 mm
2
to 2.5 mm
2
).
•
Separate cables and conduits may be required to conform to standard instrumentation
wiring practices or electrical codes.
Содержание SITRANS LR200 7ML5422
Страница 185: ...SITRANS LR200 with mA HART Operating Instructions 05 2019 A5E32337676 AE 185 B 5 4 PFTE rod antenna threaded connection ...
Страница 193: ...SITRANS LR200 with mA HART Operating Instructions 05 2019 A5E32337676 AE 193 ...
Страница 194: ...SITRANS LR200 with mA HART 194 Operating Instructions 05 2019 A5E32337676 AE ...
Страница 212: ...Index SITRANS LR200 with mA HART 212 Operating Instructions 05 2019 A5E32337676 AE ...