SITRANS LG240 - Operating Instructions
44286-EN-171021
This status message is inactive by default. It can be activated by the
user via PACTware/DTM or EDD.
The following table shows the error codes in the status message
"
Failure
" and gives information on the reason and rectification. Keep
in mind that some information is only valid for four-wire instruments.
Code
Text mes-
sage
Cause
Rectification
DevSpec State in CMD 48
F013
no measured
value avail-
able
•
Sensor does not detect an
echo during operation
•
Process component or probe
contaminated or defective
•
Check for correct mounting
and/or parameter settings
•
Clean or exchange process
component or probe
Bit 0 of Byte 0 … 5
F017
Adjustment
span too small
•
Adjustment not within specifi-
cation
•
Change adjustment accord-
ing to the limit values (differ-
ence between min. and max.
≥ 10 mm)
Bit 1 of Byte 0 … 5
F025
Error in the
linearization
table
•
Index markers are not con-
tinuously rising, for example
illogical value pairs
•
Check values of the lineari-
zation table
•
Delete/create a new lineari-
zation table
Bit 2 of Byte 0 … 5
F036
No operable
software
•
Failed or interrupted software
update
•
Repeat software update
•
Check electronics version
•
Exchanging the electronics
•
Send instrument for repair
Bit 3 of Byte 0 … 5
F040
Error in the
electronics
•
Hardware defect
•
Exchanging the electronics
•
Send instrument for repair
Bit 4 of Byte 0 … 5
F041
Probe loss
•
Probe mechanically defec-
tive
•
Check probe and exchange,
if necessary
Bit 13 of Byte 0 … 5
F080
General soft-
ware error
•
General software error
•
Disconnect operating voltage
briefly
Bit 5 of Byte 0 … 5
F105
Measured
value is deter-
mined
•
The instrument is still in the
start phase, the measured
value could not yet be
determined
•
Wait for the end of the
switch-on phase
•
Duration depending on
the version and parameter
adjustment max. 5 min.
Bit 6 of Byte 0 … 5
F113
Communica-
tion error
•
EMC interference
•
Transmission error during
external communication with
4-wire power supply unit
•
Remove EMC influences
•
Exchange 4-wire power sup-
ply unit or electronics
Bit 12 of Byte 0 … 5
F260
Error in the
calibration
•
Error in the calibration car-
ried out in the factory
•
Error in the EEPROM
•
Exchanging the electronics
•
Send instrument for repair
Bit 8 of Byte 0 … 5
F261
Error in the
instrument
settings
•
Error during setup
•
Error when carrying out a
reset
•
False signal suppression
faulty
•
Carry out a reset
•
Repeat setup
Bit 9 of Byte 0 … 5
Failure
Содержание SITRANS LG240
Страница 2: ...2 PBD 51041038 SITRANS LG240 Operating Instructions 44286 EN 171021 ...
Страница 85: ...Notes 85 PBD 51041038 SITRANS LG240 Operating Instructions 44286 EN 171021 ...
Страница 86: ...Notes 86 PBD 51041038 SITRANS LG240 Operating Instructions 44286 EN 171021 ...
Страница 87: ...Notes 87 PBD 51041038 SITRANS LG240 Operating Instructions 44286 EN 171021 ...