![Siemens SITRANS LG240 Скачать руководство пользователя страница 24](http://html.mh-extra.com/html/siemens/sitrans-lg240/sitrans-lg240_operating-instructions-manual_374496024.webp)
24
PBD-51041038
SITRANS LG240 - Operating Instructions
44286-EN-171021
5
1
2
+
( )
(-)
6 7 8
4...20mA
Display
2
3
4
1
Fig. 15: Terminal compartment - double chamber housing
1 Voltage supply, signal output
2 For display and adjustment module or interface adapter
3 For external display and adjustment unit
4 Ground terminal for connection of the cable screen
5.5 Wiring plan, Ex-d-ia double chamber housing
3
1
2
5 6 7 8
1
2
( )
(-)
+
4...20mA
Fig. 16: Electronics compartment - Ex-d-ia double chamber housing
1 Internal connection to the terminal compartment
2 For display and adjustment module or interface adapter
3 Internal connection to the plug connector for external display and adjust-
ment unit (optional)
Note:
HART multidrop mode is not possible when using an Ex-d-ia instru-
ment.
Terminal compartment