Connection drawing (FM/CSA)
The FM/CSA connection drawing number (A5E44090649A) listed on the device nameplate
can be downloaded from our website:
Product page (
www.siemens.com/sitransprobelu240
)
Go to Technical Info > Images, graphics, drawings.
6.3.1.2
Non-incendive wiring
Connection drawing (FM)
The FM connection drawing number (A5E44092290) listed on the device nameplate can be
downloaded from our website:
Product page (
www.siemens.com/sitransprobelu240
)
Go to Technical info > Images, graphics, drawings.
6.3.1.3
Further information related to hazardous area installations
● For wiring requirements follow local regulations.
● Use approved cable gland/conduit seal to maintain Type 4X, Type 6, IP66, IP68 ratings.
6.3.2
Instructions specific to hazardous area installations
6.3.2.1
Instructions in accordance with IEC 60079-0:2011 clause 30
The following instructions relevant to safe use in a hazardous area apply to equipment covered
by certificate numbers Sira 18ATEX2045X and IECEx SIR 18.0013X.
1. The certification marking is as follows:
Certificate number:
IECEx SIR 18.0013X
Sira 18ATEX2045X
Certification code:
Ex ia IIC T4 Ga
Ex ia IIC T4 Ga
Other marking:
2. The equipment may be used in zones 0, 1 & 2 with flammable gases and vapours with
apparatus groups IIA, IIB & IIC and with temperature classes T4.
3. The equipment is only certified for use in ambient temperatures in the range -40 ºC to +80 ºC
and should not be used outside this range.
4. Installation shall be carried out in accordance with the applicable code of practice by
suitably-trained personnel.
5. There are no special checking or maintenance conditions other than a periodic check.
6. With regard to explosion safety, it is not necessary to check for correct operation.
Connecting
6.3 Hazardous area installations
SITRANS Probe LU240 with mA/HART
Compact Operating Instructions, 10/2018, A5E42673704-AB
27