![Siemens SITRANS FC430 Скачать руководство пользователя страница 263](http://html.mh-extra.com/html/siemens/sitrans-fc430/sitrans-fc430_operating-instructions-manual_374486263.webp)
Technical reference
A
A.1
Sensor dimension dependent default settings
Mass flow
Sensor type
Sensor size
Default value
Unit:
Kg/s
Upper Limit Alarm and Upper Limit Warning
FC400
DN 15
2,209
DN 25
6,136
DN 50
24,54
DN 80
62,83
DN 100
180,56
DN 150
298,61
MASS2100
1
0,010
1.5
0,022
2.1
0,043
3
0,088
FC300 DN4 HP
2
0,039
FC300 DN4 C22
3
0,088
FC300 DN4 316
3.5
0,120
MASS2100
6
0,353
15
2,209
Sensor type
Sensor size
Default value
Unit:
Kg/s
Lower Limit Alarm and Lower Limit Warning
FC400
DN 15
-2,209
DN 25
-6,136
DN 50
-24,54
DN 80
-62,83
DN 100
-180,56
DN 150
-298,61
MASS2100
1
-0,010
1.5
-0,022
2.1
-0,043
3
-0,088
FC300 DN4 HP
2
-0,039
FC300 DN4 C22
3
-0,088
FC300 DN4 316
3.5
-0,120
FC430 (From firmware 4.0)
Operating Instructions, 06/2017, A5E39789392-AA
263
Содержание SITRANS FC430
Страница 40: ...Description 3 5 Theory of operation FC430 From firmware 4 0 40 Operating Instructions 06 2017 A5E39789392 AA ...
Страница 94: ...Connecting 5 4 Device nameplates FC430 From firmware 4 0 94 Operating Instructions 06 2017 A5E39789392 AA ...
Страница 150: ...Operating FC430 7 2 HMI FC430 From firmware 4 0 150 Operating Instructions 06 2017 A5E39789392 AA ...
Страница 182: ...Functions 8 16 Maintenance FC430 From firmware 4 0 182 Operating Instructions 06 2017 A5E39789392 AA ...
Страница 262: ...Dimensions and weight 12 5 Mounting bracket FC430 From firmware 4 0 262 Operating Instructions 06 2017 A5E39789392 AA ...
Страница 534: ...Index FC430 From firmware 4 0 534 Operating Instructions 06 2017 A5E39789392 AA ...