Functions
7.6 Totalizer
FC410 with Modbus
Operating Instructions, 02/2016, A5E33120874-AC
75
7.6
Totalizer
Totalizer function
The device has one totalizer function that can be used to totalize the massflow process
value.
The totalizer may be paused, resumed or reset:
●
Pause (Modbus address 2613): the totalizer holds the last value before the failure
occurred
●
Resume (Modbus address 2614): the totalizer continues counting the actual measured
value
●
Reset (Modbus address 2612): the totalizer continues counting based on the last input
value (for example massflow) before the failure occurred.
Note
The totalizer is reset on power failure.
7.7
Access management
All parameters may be viewed, but some are protected against changes by access level
control.
The Access Management menu makes it possible to gain access to PIN code protected
parameters and to change PIN codes.
Image 7-6
Access Management menu
Содержание SITRANS FC410
Страница 2: ......
Страница 70: ...Commissioning 6 14 Process variables FC410 with Modbus 68 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 92: ...Troubleshooting FAQs 10 2 Troubleshooting FC410 with Modbus 90 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 142: ...Sensor dimension dependent default settings FC410 with Modbus 140 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 146: ...Zero point adjustment FC410 with Modbus 144 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 150: ...CRC calculation FC410 with Modbus 148 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 152: ...Exception codes E 1 Exception handling FC410 with Modbus 150 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 154: ...Float definition F 1 Float definition FC410 with Modbus 152 Operating Instructions 02 2016 A5E33120874 AC ...