FM:
Sensor with Mini Flow Link (MFL) (FC410):
Class I, II, III Division 1
Groups A, B,C, D, E, F, G
Class I Zone1 and Zone 20/21
Note
Control drawing
See Control drawing: A5E31205486A
Maximum temperature specifications for Ex use
Device temperature classification with and without dust is related to the process temperature
and ambient temperature as listed below.
The maximum allowable process fluid temperatures with respect to temperature class for the
device when used with potentially explosive gases in a maximum ambient temperature of
+60°C are:
Ta (°C)
Maximum Process Temperature per Temperature Class (°C)
T6
T5
T4
T3
60
70
70
70
70
55
85
100
100
100
50
85
100
130
130
45
85
100
135
160
40
85
100
135
190
35
85
100
135
200
30
85
100
135
200
If the equipment is placed in a "tb" environment (Zone 21), the maximum process
temperatures shall be as follows:
Ta (°C)
Maximum Process Temperature per Temperature Class (°C)
60
70
55
100
50
130
45
160
40
190
35
200
30
200
Additionally, the maximum surface temperature of the overall device shall be:
●
If Tprocess ≤ 85°C, maximum surface temperature = 85°C.
●
If Tprocess > 85°C, maximum surface temperature = process temperature.
Содержание SITRANS FC410
Страница 2: ......
Страница 70: ...Commissioning 6 14 Process variables FC410 with Modbus 68 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 92: ...Troubleshooting FAQs 10 2 Troubleshooting FC410 with Modbus 90 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 142: ...Sensor dimension dependent default settings FC410 with Modbus 140 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 146: ...Zero point adjustment FC410 with Modbus 144 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 150: ...CRC calculation FC410 with Modbus 148 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 152: ...Exception codes E 1 Exception handling FC410 with Modbus 150 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 154: ...Float definition F 1 Float definition FC410 with Modbus 152 Operating Instructions 02 2016 A5E33120874 AC ...