Technical data
11.8 Design
FC410 with Modbus
Operating Instructions, 02/2016, A5E33120874-AC
99
11.8
Design
Table 11- 25 Design
Description
Specification
Dimension and weight
See Dimensions and weight (Page 111)
Process connectors
•
EN1092-1 B1, PN16, PN40, PN63, PN100,
PN160
•
EN1092-1 D (gasket groove), PN40, PN63,
PN100, PN160
•
ISO 228-1 G *
•
ASME B1.20.1 NPT *
•
ASME B16.5, Cl 150, Cl 300, Cl 600, Cl 900
•
DIN 11851 **
•
DIN 32676 *
•
DIN 11864-1A **, DIN 11864-2C (inch) **, DIN
11864-3A **
•
ISO 2852 **
•
ISO 2853 **
•
JIS B 2220, 10K, 20K, 40K, 62K
Electrical connection
•
M12 connector with 4-wire cable
•
Standard cable with polymer / brass / stain-
less steel cable glands (metric or NPT)
•
Armored cable with stainless steel armored
cable glands (metric or NPT)
•
Conduit entries (metric or NPT)
Material
Measuring tubes
•
AISI 316L / W1.4404
•
Hastelloy C22 / UNS N06022
Process connectors
•
Standard:
–
AISI 316L / W1.4435 or W1.4404
–
Hastelloy C22 / UNS N06022
•
Hygienic:
–
AISI 316L / W1.4435
Sensor enclosure
AISI 304 / W1.4301
Transmitter enclosure
Aluminum with corrosion-resistant coating
Measuring tube design
Split flow through 2 parallel tubes with combined
cross-section area 50% of the nominal pipe
The measuring tubes are bent in a trapezoidal
curve
Содержание SITRANS FC410
Страница 2: ......
Страница 70: ...Commissioning 6 14 Process variables FC410 with Modbus 68 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 92: ...Troubleshooting FAQs 10 2 Troubleshooting FC410 with Modbus 90 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 142: ...Sensor dimension dependent default settings FC410 with Modbus 140 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 146: ...Zero point adjustment FC410 with Modbus 144 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 150: ...CRC calculation FC410 with Modbus 148 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 152: ...Exception codes E 1 Exception handling FC410 with Modbus 150 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 154: ...Float definition F 1 Float definition FC410 with Modbus 152 Operating Instructions 02 2016 A5E33120874 AC ...