BACnet Communications
3.2 BACnet Protocol Implementation Conformance Statement
F US Clamp-on Communications Protocol Manual
Hardware Installation Manual, 11/2015, A5E34981613-AC
31
Binary Input Object
Property Identifier
Description and/or Example Value
Object_Identifier
Unique Identifier (e.g. 20971525)
R
Object_Name
(see list of Binary Input objects)
(e.g. C1_Pipe_Empty)
R
Object_Type
3 – Binary Input
R
Present_Value
R
Description
Character String (e.g. C1_Pipe_Empty)
R
Status_Flags
IN_ALARM,FAULT,OVERRIDDEN,OUT_OF_SERVICE
(e.g. 0000)
R
Event_State
0 - Normal
R
Out_Of_Service
0 - False
R
Reliability
0
R
Active Text
Active
R
Inactive Text
Inactive
R
3.2
BACnet Protocol Implementation Conformance Statement
A BACnet Conformance Statement is included with each communications module. It is a
reference for the installer that lists the applicable specifications for each individual BACnet
communications setup.
Typical BACnet Conformance Statement
Date:
January, 2012
Vendor Name:
Siemens Industry, Inc.
Product Name:
SITRANS F US Clamp-On Ultrasonic
Flowmeters
Product Model Number:
Siemens Option Card
Application Software Version:
V6.11b (A)
Firmware Revision:
2.04.06
BACnet Protocol Revision:
1
Product Description:
Clamp-on ultrasonic flowmeter
BACnet Standardized Device Profile (Annex L):
☐
BACnet Operator Workstation (B-OWS)
☐
BACnet Advanced Operator Workstation (B-
AWS)
☐
BACnet Operator Display (B-OD)
☐
BACnet Building Controller (B-BC)
☐
BACnet Advanced Application Controller (B-
AAC)
☑
BACnet Application Specific Controller (B-ASC)
☐
BACnet Smart Sensor (B-SS)
☐
BACnet Smart Actuator (B-SA)
List all BACnet Interoperability Building Blocks Supported (Annex K):