Installing/Mounting
2.2 F US Clamp-on Communications Module Installation
F US Clamp-on Communications Protocol Manual
12
Hardware Installation Manual, 11/2015, A5E34981613-AC
6.
Place the Communications Module over the I/O Module and align connector J3 with P1 of
the I/O Module (figure 2-2).
①
Ethernet Connector J5
⑤
RS-485 Connector J1
②
SW1
⑥
Captive Screw and Standoff
③
SW2
⑦
Standoff
④
J3
Figure 2-2
SITRANS F US Clamp-on Communications Module A5E31949269
7.
Gently press the Communications Module down to connect it to the I/O Module.
8.
Tighten the captive screws to secure the Communications Module and I/O Module.
9.
If using Ethernet IP, connect the Ethernet connector.
Note
Ethernet Web Utility Toolbox
This Web utility is used to change settings including IP addresses for multiple metes and
to locate communications modules on the same network.
The web utility can be found at
http://www.fieldserver.com/techsupport/utility/downloads.php
http://www.fieldserver.com/techsupport/utility/downloads.php. //
XmlEditor.InternalXmlClipboard:6489c307-3482-c2fd-cc08-262dd24d5093
The default IP address is: 192.168.0.2
Note
RS-485 can be used for all communication protocols except HART.
10.If using RS-485, connect RS-485 connector to J1.
11.Referring back to figure 2-1, after Communications Module installation is complete, place
the new Communications Module cover supplied in the mounting kit over the board and
tighten the captive screw
②
.
12.Close the flowmeter cover and secure the side latch.