Modbus communication
A.9 Modbus holding registers tables
SITRANS F Ultrasonic flowmeters FST030 (Modbus)
324
Operating Instructions, 08/2017, A5E37367739-AC
Channel 3 output current
Table A- 122 Channel 3 output current
Modbus
register
Data type /
Size in bytes
Parameter
Description
Default value
[unit]
(unit register)
Value range /
Setting options
Access
level
9125
Unsigned / 2 Simulation
Enables or disables
simulation of channel 3
output current.
0
•
0: Disabled
•
1: Enabled
Read /
write
9126
Float / 4
Simulated value Current value that is
output on the channel
when simulation is
enabled.
0
[mA]
0 - 25
Read /
write
Channel 3 output status
Table A- 123 Channel 3 output status
Modbus
register
Data type /
Size in bytes
Parameter
Description
Default value
[unit]
(unit register)
Value range /
Setting options
Access
level
9164
Unsigned / 2 Simulation
Enables or disables
simulation of channel 3
output status.
0
•
0: Disabled
•
1: Enabled
Read /
write
9165
Unsigned / 2 Simulated value Signal level that is
output on the channel
when simulation is
enabled.
0
0, 1
Read /
write
Channel 3 output frequency
Table A- 124 Channel 3 output frequency
Modbus
register
Data type /
Size in bytes
Parameter
Description
Default value
[unit]
(unit register)
Value range /
Setting options
Access
level
9205
Unsigned / 2 Simulation
Enables or disables
simulation of channel 3
output frequency.
0
•
0: Disabled
•
1: Enabled
Read /
write
9206
Float / 4
Simulated value Frequency value that is
output on the channel
when simulation is
enabled.
1.0
[Hz]
0.0 - 12500.0
Read /
write