Modbus communication
A.9 Modbus holding registers tables
SITRANS F Ultrasonic flowmeters FST030 (Modbus)
272
Operating Instructions, 08/2017, A5E37367739-AC
Modbus
register
Data type /
Size in bytes
Parameter
Description
Default value
[unit]
(unit register)
Value range /
Setting options
Access
level
9040
Unsigned / 2 Status icons
Type of alarm icons
shown in local display.
Order-
specific.
•
0: Standard (Sie-
mens)
•
1: NAMUR
Read /
write
6409
Float / 4
Filter time con-
stant
Damping filter time for
process values to be
displayed.
1.0
0.0 - 100.0
Read /
write
6411
Unsigned / 4 Process values
(1)
Bit encoded selection
group 1 of process
values the display
damping filter impacts.
(Page 285).
0xFFFE37FF -
Read /
write
6413
Unsigned / 4 Process values
(2)
Bit encoded selection
group 2 of process
values the display
damping filter impacts.
(Page 285).
0x00001E7F -
Read /
write
View 1 settings
Table A- 72 View 1 settings
Modbus
register
Data type /
Size in bytes
Parameter
Description
Default value
[unit]
(unit register)
Value range /
Setting options
Access
level
9007
Unsigned / 2 View
Type of appearance.
3
•
1: Single value.
•
3: Three values.
•
6: 1 value and bar
graph.
•
7: 1 value and graph.
•
8: Six values.
•
9: Six diagnostic
values.
Read /
write
9018
Unsigned / 2 1
st
value
Selection of the first
value.
0
Read /
write
9019
Unsigned / 2 2
nd
value
Selection of the second
value. Depending on
the number of values.
2
Read /
write
9020
Unsigned / 2 3
rd
value
Selection of the third
value. Depending on
the number of values.
3
Read /
write