Modbus communication
A.9 Modbus holding registers tables
SITRANS F Ultrasonic flowmeters FST030 (Modbus)
Operating Instructions, 08/2017, A5E37367739-AC
213
Modbus
register
Data type /
Size in bytes
Parameter
Description
Default value
[units]
(units regis-
ter)
Value range /
Setting options
Access
level
8961
Unsigned / 2 Fail-safe behav-
ior
Pulse output reaction
in case of a fault.
2
•
0: Last valid value
•
1: Hold. Value 0.0
substitutes the actual
input value
•
2: Disabled
•
3: Custom value
•
4: Maximum pulses/s
on CH2 and no puls-
es on CH3. Only if
CH3 is configured to
redundancy mode
Read /
write
7421
Float / 4
Fail-safe value Output value in case of
a fault and when Fail-
safe behavior (8939) is
configured to 4.
0.0
[pulses/s]
0.0 - 12500.0
Read /
write
7151
Float / 4
Forced value
Forced value when
forcing is active.
1.0
[pulses/s]
0.0 - 12500.0
Read /
write
Channel 2 status output settings
Table A- 52 Channel 2 status output settings
Modbus
register
Data type /
Size in bytes
Parameter
Description
Default value
[units]
(units regis-
ter)
Value range /
Setting options
Access
level
8841
Unsigned / 2 Status mode
Select the functionality
for the status output.
0
•
0: Alarm class
•
1: Alarm item
Read /
write
8858
Unsigned / 2 Alarm class
Bit encoded selection
of alarm classes which
impact the status out-
put. Each diagnostic
event is allocated to an
alarm class. See Alarm
items (Page 295).
Applicable if Status
mode = 0.
0
•
Bit 0: Process value
alarm (PA)
•
Bit 1: Process value
warning (PW)
•
Bit 2: Maintenance
alarm (MA)
•
Bit 3: Maintenance
warning (MW)
•
Bit 4: Maintenance
required (MR)
•
Bit 5: Function check
(FC)
Read /
write