Channel 3
Table 4-84
Channel 3
Modbus
register
Data type /
Size in bytes
Parameter
Description
Default value
[unit]
(unit register)
Value range /
Setting options
Access
level
9103
Float / 4
Current output
value
Output current value if
configured to current
output.
-
-
Read
only
9128
Unsigned / 2
Error status
Error status if config‐
ured to current output.
-
● Bit 0: Overflow
● Bit 1: Underflow
● Bit 2: Fail mode
activated
● Bit 3: Cable break
● Bit 4: Output current
cannot be
established (read
back deviation > 0.1
mA)
Read
only
9140
Unsigned / 2
Status output
Status value if config‐
ured to status output.
-
-
Read
only
9269
Float / 4
Pulse status
output
Amount done if config‐
ured to pulse output.
-
-
Read
only
9272
Unsigned / 2
Error status
Error status if config‐
ured to pulse output.
-
● Bit 0: The pulse
output has reached
the maximum pulse
output frequency
● Bit 1: Fail mode is
activated
Read
only
9287
Unsigned / 4
Pulse counter
Pulse output since
startup.
-
-
Read
only
9200
Float / 4
Frequency out‐
put value
Frequency value if con‐
figured to frequency
output.
-
-
Read
only
9203
Unsigned / 2
Error status
Error status if config‐
ured to frequency out‐
put.
-
● Bit 0: Overflow
● Bit 1: Underflow
● Bit 2: Fail mode
activated
Read
only
10503
Float / 4
Current input
value
Input current value if
configured to current in‐
put.
-
-
Read
only
MODBUS commands
4.10 Modbus holding registers tables
FCT030 Modbus (From firmware 4.0)
Function Manual, 06/2018, A5E39931813-AB
167
Содержание SITRANS F Coriolis FCT030
Страница 6: ...Table of contents FCT030 Modbus From firmware 4 0 6 Function Manual 06 2018 A5E39931813 AB ...
Страница 16: ...Communication 2 4 Connecting FCT030 Modbus From firmware 4 0 16 Function Manual 06 2018 A5E39931813 AB ...
Страница 194: ...Definitions A 1 Definitions FCT030 Modbus From firmware 4 0 194 Function Manual 06 2018 A5E39931813 AB ...
Страница 198: ...Index FCT030 Modbus From firmware 4 0 198 Function Manual 06 2018 A5E39931813 AB ...