Operation
6.4 Parameter menu
SITRANS DA400 for material flow monitoring with protection against explosion
Operating Instructions, 09/2007, A5E00841152-01
49
6.4.2
Parameter list
Parameter
no.
Parameter
name
Parameter value
Factory
setting
Meaning
P. 0
SWREV
3.00.00
SW version (not adjustable)
oFF
Acoustic channel 1
oFF
Channel switched off
on L
Channel in measurement mode, normal
measuring sensitivity
on H
Channel in measurement mode, normal
measuring sensitivity, pre and main alarm
received in event of sensor fault
SIMU
Channel in simulation mode
P. 1
SoCH1
tESt
Channel in test mode
P. 2
SoCH2
oFF, on L, on H
oFF
Acoustic channel 2 / See P.1
P. 3
SoCH3
oFF, on L, on H
oFF
Acoustic channel 3 / See P.1
P. 4
SoCH4
oFF, on L, on H
oFF
Acoustic channel 4 / See P.1
P. 5
PrAL1
0 to 99.9
99.9
Pre-alarm channel 1
P. 6
AL1
0 to 99.9
99.9
Main alarm channel 1
P. 7
PrAL2
0 to 99.9
99.9
Pre-alarm channel 2
P. 8
AL2
0 to 99.9
99.9
Main alarm channel 2
P. 9
PrAL3
0 to 99.9
99.9
Pre-alarm channel 3
P.10
AL3
0 to 99.9
99.9
Main alarm channel 3
P.11
PrAL4
0 to 99.9
99.9
Pre-alarm channel 4
P.12
AL4
0 to 99.9
99.9
Main alarm channel 4
P.13
TIME
0 to 9999
0
Response time for alarms coming from
acoustic channels in seconds
oFF
Type of alarm acknowledgement
oFF
Alarm not stored, no acknowledgement
¬St.Ac
Alarm not stored, acknowledgement stops
until next response
P.14
AcK
St.Ac
Alarm stored, acknowledgement stops until
next response
P.15
doPR1
oFF, do1, do2, do3, do4, do5,
do6, ¬do1, ¬do2, ¬do3, ¬d04,
¬do5, ¬do6
oFF
Status signal assignment:
Pre-alarm 1 to hardware output
(do : digital output / ¬ : inverse)
P.16
doAL1
As P.15
do1
Main alarm 1
P.17
doPR2
As P.15
oFF
Pre-alarm 2
P.18
doAL2
As P.15
do2
Main alarm 2
P.19
doPR3
As P.15
oFF
Pre-alarm 3
P.20
doAL3
As P.15
do3
Main alarm 3
P.21
doPR4
As P.15
oFF
Pre-alarm 4
P.22
doAL4
As P.15
do4
Main alarm 4
P.23
doFAI
As P.15
oFF
Input fault summation signal
P.24
doFAu
As P.15
oFF
Internal fault summation signal