![Siemens SITRANS AW 7MP3112 Series Скачать руководство пользователя страница 54](http://html.mh-extra.com/html/siemens/sitrans-aw-7mp3112-series/sitrans-aw-7mp3112-series_operating-instructions-manual_1265484054.webp)
The following list contains information about the structure of these input boxes and the format
in which you can enter information in these boxes:
Parameter
Meaning
Example
Default
Polling address
HART address of the WirelessHART adapter.
● Default setting 15
● Range 0 ... -63
63
15
Master mode
In a current loop, a device configurator such as
SIMATIC PDM and the WirelessHART adapter
(as examples) must be assigned different HART
master types.
● The default setting is primary master
● There is a primary master and a secondary
master.
● If you connect a device configurator or a an‐
other master/host, this must be set to secon‐
dary master.
Primary master
Num. response pream‐
bles
Number of preambles sent at the start of the HART
frame to synchronize wired communication.
● Range 5 ... 20
5
Retry count
Number of attempts made by the WirelessHART
adapter to establish communication with the con‐
nected field device before a connection error is
signaled.
3
3
Lowest scan address
Address at which the WirelessHART adapter be‐
gins to search for connected field devices.
0
0
Highest scan address
Address up to which the WirelessHART adapter
scans for connected field devices.
1
1
9.5
Illustration of the device variables of the adapter
The WirelessHART adapter can output the value and status of various variables. Four variables
can be represented in the network. They can be represented and configured with
SIMATIC PDM.
The following list contains information about the structure of these input boxes and the format
in which you can enter information in these boxes:
Parameter
Meaning
Example
Default
Primary variable
First variable
● The variable is linked directly to the meas‐
ured current value.
Unit of the primary vari‐
able
Unit of the primary variable
l
mA
Secondary variable
Second variable
Temperature
Temperature
Unit of the secondary
variable
Unit of the secondary variable
°C
°C
Tertiary variable
Third variable
Battery voltage
Battery voltage
Parameter assignment/addressing
9.5 Illustration of the device variables of the adapter
WirelessHART Adapter SITRANS AW200
54
Operating Instructions, 02/2020, A5E02777161-AA