![Siemens SITRANS 7MP1110-0AC Скачать руководство пользователя страница 44](http://html.mh-extra.com/html/siemens/sitrans-7mp1110-0ac/sitrans-7mp1110-0ac_operating-instructions-manual_384651044.webp)
Operation
5.6 Parameter descriptions
SITRANS TF280 WirelessHART
44
Operating Instructions, 10/2010, A5E02619566-02
5.6
Parameter descriptions
5.6.1
"1 Quick start"
5.6.1.1
"1.1 Network ID"
Factory setting:
1229
Setting range:
00001 ... 65535
Purpose:
Assign network ID
Description:
Commissioning requirement. Password-protected function.
For security reasons, always change this during commissioning.
5.6.1.2
"1.2 Network key"
Factory setting:
-
Setting range:
32-digit, hexadecimal
Purpose:
Assign network key
Description:
Commissioning requirement. Must be assigned and set by the user during
commissioning.
5.6.1.3
"1.3 Device name"
Factory setting:
-
Setting range:
-
Purpose:
Specify device name
Description:
The device name can contain up to 8 characters. Select the characters by
pressing the ↑ or ↓ key.
5.6.1.4
"1.4 Transmission rate"
Factory setting:
60 s
Setting range:
8 to 255 s
Purpose:
Set transmission rate.
Setting of time intervals at which the transmitter sends measured values.
Increase or decrease the parameter value by pressing the ↑ or ↓ key.
Description:
Use the parameter "2.1.2 Burst display" (Page 46) to visualize the set
transmission rate.