SITOP PSU8200 1ph
Manual, 11.2014, C98130-A7633-A1-3-7629
53
Ambient conditions
8
6EP3333-8SB00-0AY0 (24 V/5 A)
6EP3334-8SB00-0AY0 (24 V/10 A)
6EP1336-3BA10 (24 V/20 A)
Ambient temperature
-25 ... +70° C with natural convection
Tested according to:
•
EN 60068-2-1 cold
•
EN 60068-2-2 dry heat
•
EN 60068-2-78 humid heat, constant
•
EN 60068-2-14 temperature change
Transport and storage
temperature
-40 ...+85 °C
Tests (packed for shipping) according to:
•
EN 60068-2-1 cold
•
EN 60068-2-2 dry heat
•
EN 60068-2-30 humid heat, cyclic
Humidity class
Climatic class 3K3 according to EN 60721, without condensation
Degree of pollution
2
Mechanical stressing
during operation
Tested according to:
•
EN 60068-2-6 vibration, test Fc:
7 mm deflection in the range 5 ... 8.4 Hz
2 g acceleration in the range 8.4 ... 150 Hz
•
EN 60068-2-27 shock, test Ea: Acceleration 150 m/s
2
, test duration 11 ms
Damaging gases
Tested according to:
•
EN 60068-2-42 sulfur dioxide
•
EN 60068-2-43 hydrogen sulfide
Atmospheric pressure Operation:
•
1080 ... 795 hPa (-1000 ... +2000 m)
•
For operation at installation altitudes from 2000 m up to 6000 m: Output power derating of -
7.5 % / 1000 m or reduction of the ambient temperature by 5 K / 1000 m
see Figure 4-4 Mounting height derating (Page 26)
•
Overvoltage category:
III to 2000 m (EN 50178)
II from 2000 m to 6000 m (EN 50178)
II to 2000 m (EN 60950-1)
I from 2000 m to 6000 m (EN 60950-1)
Storage:
•
1080 ... 660 hPa (-1000 ... +3500 m)
Содержание SITOP PSU8200
Страница 8: ...Safety instructions SITOP PSU8200 1ph 8 Manual 11 2014 C98130 A7633 A1 3 7629 ...
Страница 36: ...Installation 5 2 Output side connection SITOP PSU8200 1ph 36 Manual 11 2014 C98130 A7633 A1 3 7629 ...
Страница 48: ...Technical data 6 9 Dimension drawing SITOP PSU8200 1ph 48 Manual 11 2014 C98130 A7633 A1 3 7629 ...
Страница 54: ......
Страница 64: ...Environment SITOP PSU8200 1ph 64 Manual 11 2014 C98130 A7633 A1 3 7629 ...