6EP3323-7SB00-0AX0 (12 V/7 A), 6EP3324-7SB00-3AX0 (12 V/12 A),
6EP3333-7LB00-0AX0 (24 V/3,7 A), 6EP3333-7SB00-0AX0 (24 V/5 A),
6EP3334-7SB00-3AX0 (24 V/10 A), 6EP3336-7SB00-3AX0 (24 V/20 A)
Status display
LED green for 12 V O.K. or 24 V O.K.
Yellow LED
Signaling contact (13, 14)
Relay contact (NO contact, contact rating (isolated) 24 V AC/0.1 A; 30 V DC/0.1 A
Device without diagnostics monitor
Figure 2-5
Signaling, signaling contact
Signaling
Signaling contact
6EP3323-7SB00-0AX0 (12 V/7 A)
6EP3333-7LB00-0AX0 (24 V/3.7 A)
6EP3333-7SB00-0AX0 (24 V/5 A)
LED "O.K.":
green:
green flashing (0.5 Hz):
Output voltage U
out
> 10 V or
U
out
> 11.8 V
shutdown as a result of thermal overload
Output voltage U
out
> 20 V or
U
out
> 23 V
shutdown as a result of thermal overload
Signaling contact (13, 14)
closed:
Output voltage U
out
> 10 V
contact rating: 24 V AC/0.1 A; 30 V DC/0.1 A
NOTICE: It is not permissible that the signal-
ing contact is connected on the primary side!
Output voltage U
out
> 20 V
contact rating 24 V AC/0.1 A; 30 V DC/0.1 A
NOTICE: It is not permissible that the signal-
ing contact is connected on the primary side!
Содержание SITOP PSU6200
Страница 8: ...Notes on safety SITOP PSU6200 1ph 8 Manual 03 2019 A5E44623264 1 76 ...
Страница 22: ...Mounting removal SITOP PSU6200 1ph 22 Manual 03 2019 A5E44623264 1 76 ...
Страница 42: ...Installation 5 2 Output side connection SITOP PSU6200 1ph 42 Manual 03 2019 A5E44623264 1 76 ...
Страница 74: ...Environment SITOP PSU6200 1ph 74 Manual 03 2019 A5E44623264 1 76 ...