SITOP PSU100L
Manual, 08.2016, C98130-A7603-A1-2-7629
21
Mounting position, mounting clearances
4
4.1
Standard mounting position
The device is mounted on standard mounting rails according to EN 60715 35×7,5/15. The
device must be mounted vertically in such a way that the input terminals and the output
terminals are at the bottom to ensure correct cooling.
A clearance of at least 50 mm should be maintained above and below the device.
No space is required at the side.
Output current as a function of the ambient temperature and mounting height
Figure 4-1
6EP1332-1LB00 mounting position
Figure 4-2
6EP1333-1LB00 mounting position