Engineering and remote access
7.3 SIMATIC STEP 7 in the TIA Portal
PSU8600power supply systems
136
Manual, 04.2016, A5E35883207-7-76
7.3.6.3
Parameterizing outputs
The procedure is the same for all parameters. The individual parameters and their possible
values are described in the following sections.
Preconditions
●
The SITOP PSU8600 was integrated in the opened project.
●
When configuring an expansion module, this must be assigned to the SITOP PSU8600.
Procedure
1.
Select the SITOP PSU8600 or the expansion module in the Device view.
2.
In the inspector window in the navigation area, open the range of the required output.
3.
You can see the possible subgroups for parameterization.
Output parameters
Parameter
Value range
Default setting
Setpoint output voltage
4 - 28 V
24.0 V
Response threshold of the output current
0 - 10 A or 0 - 5 A
10 A or 5 A
Prewarning threshold output current
0 - 100 %
90 %
On delay
Variable
Dependent on the settings
in the basic device
Mode
ELECTRONIC
SHUTDOWN / CONSTAN
T CURRENT
ELECTRONIC
SHUTDOWN
Содержание SITOP BUF8600
Страница 6: ...Overview PSU8600power supply systems 6 Manual 04 2016 A5E35883207 7 76 ...
Страница 12: ...Safety instructions PSU8600power supply systems 12 Manual 04 2016 A5E35883207 7 76 ...
Страница 164: ...Engineering and remote access 7 4 SIMATIC STEP 7 PSU8600power supply systems 164 Manual 04 2016 A5E35883207 7 76 ...
Страница 240: ...Technical data 9 9 Dimension drawings PSU8600power supply systems 240 Manual 04 2016 A5E35883207 7 76 ...
Страница 246: ...Environmental conditions PSU8600power supply systems 246 Manual 04 2016 A5E35883207 7 76 ...
Страница 250: ...Environment PSU8600power supply systems 250 Manual 04 2016 A5E35883207 7 76 ...