8.7.3 Site altitude
If the site altitude is above 1000 m, the following are necessary:
• A reduction in the rated current for thermal reasons
• A reduction in the rated voltage on account of the diminished dielectric
strength
Reductions as a func-
tion of site altitude
The diagram below plots the reductions in rated current and rated operating
voltage as a function of site altitude:
Figure 8-25: Reductions as a function of site altitude
0
500
1000
1500
2000
2500
3000
3500
4000
70
75
80
85
90
95
100
105
Ue reduction
Ie reduction
Site altitude in m