Functions
3.18 Cold run
M200D PROFIBUS/PROFINET
80
Manual, 08/2014, A5E01577426A/RS-AA/004
3.18
Cold run
Description
This function enables activation of the motor without main power supply. The motor starter
responds here as if the main power supply were connected to the system. Thus, in the
commissioning phase, for example, the relevant control commands are accepted from the
controller and the relevant messages are sent.
Note
If the main power supply is nevertheless present (current flowing), an internal trip command
is generated.
The "cold run" function can be activated as follows:
●
Input action "cold run"
●
Commands: Cold run ON /OFF
If the "cold run" function is active, the motor switches off if
●
A current flow is detected
●
Main power supply is detected.
Messages and actions
Message
Action
Cold start active
—
Cold start tripping
Tripping (acknowledgment via trip reset)
Содержание SIRIUS M200D
Страница 2: ......
Страница 16: ...Product description 1 3 PROFIenergy M200D PROFIBUS PROFINET 16 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 24: ...Product family 2 3 Design concept M200D PROFIBUS PROFINET 24 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 90: ...Functions 3 22 Logbook M200D PROFIBUS PROFINET 90 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 118: ...Mounting connection 4 2 Connection M200D PROFIBUS PROFINET 118 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 222: ...Appendix A 2 Order numbers M200D PROFIBUS PROFINET 222 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 224: ...Correction sheet M200D PROFIBUS PROFINET 224 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 232: ...Index M200D PROFIBUS PROFINET 232 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 233: ......