Appendix
A.1 Data formats and data sets
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
195
A.1.4
DS68 - Read/write process output image
Note
Please note that data set 68 is overwritten by the cyclic process image in automatic mode!
Byte
Content
Value / value range
Meaning
Preamble
0
Coordination
0x21
Write via acyclic bus channel (PLC)
1
Reserved
0x00
—
2
Reserved
0x00
—
3
Reserved
0x00
—
Process output image
4
Process data
DO 0.0 to DO 0.7
See table below
5
Process data
DO 1.0 to DO 1.7
See table below
6
Reserved
0x00
—
7
Reserved
0x00
—
Table A- 1
Content of process image of the outputs (in bytes 4 and 5)
Byte.Bit
Encoding
Process data Meaning
Relevant for
4.0
Bit (1 = active) DO 0.0
Motor CW
All
4.1
DO 0.1
Motor CCW
.RS..
4.2
DO 0.2
Activation of brake
All with BO
1)
4.3
DO 0.3
Trip reset
All
4.4
DO 0.4
Emergency start
All
4.5
DO 0.5
Self-test
All
4.6
DO 0.6
—
—
4.7
DO 0.7
—
—
5.0
Bit (1 = active) DO 1.0
Output 1
All
5.1
DO 1.1
Output 2
All
5.2
DO 1.2
—
—
5.3
DO 1.3
—
—
5.4
DO 1.4
—
—
5.5
DO 1.5
—
—
5.6
DO 1.6
—
—
5.7
DO 1.7
Disable quick stop
All
1)
BO: Brake output
Содержание SIRIUS M200D
Страница 2: ......
Страница 16: ...Product description 1 3 PROFIenergy M200D PROFIBUS PROFINET 16 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 24: ...Product family 2 3 Design concept M200D PROFIBUS PROFINET 24 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 90: ...Functions 3 22 Logbook M200D PROFIBUS PROFINET 90 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 118: ...Mounting connection 4 2 Connection M200D PROFIBUS PROFINET 118 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 222: ...Appendix A 2 Order numbers M200D PROFIBUS PROFINET 222 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 224: ...Correction sheet M200D PROFIBUS PROFINET 224 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 232: ...Index M200D PROFIBUS PROFINET 232 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 233: ......