Diagnostics
7.1 Diagnostics with LED
M200D PROFIBUS/PROFINET
140
Manual, 08/2014, A5E01577426A/RS-AA/004
7.1
Diagnostics with LED
7.1.1
Statuses of the individual LEDs
The following LEDs indicate the status of the motor starter:
Figure 7-1
Diagnostic LEDs
SF LED (possible colors: red / OFF)
Status
Meaning
Possible causes
Off
No error
No error is present
Red
Device detects error Device error:
•
Current flowing with no ON command
•
Self-test error
System error:
•
Current not flowing despite ON command
(residual current detected)
•
Thermal motor model overload
1)
•
Temperature sensor overload
1)
•
Asymmetry detected
1)
•
Current limit violation
1)
•
Connector monitoring
1)
•
Circuit breaker tripped/switched off
1)
•
Group fault via output action
•
External encoder supply short-circuit
•
Internal trip
•
No switching element supply voltage (DC24V S)
1)
•
No electronics supply voltage (D24-V-NS)
1)
Start-up fault:
•
Start-up parameters missing
1)
Depends on the parameter assignment
Содержание SIRIUS M200D
Страница 2: ......
Страница 16: ...Product description 1 3 PROFIenergy M200D PROFIBUS PROFINET 16 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 24: ...Product family 2 3 Design concept M200D PROFIBUS PROFINET 24 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 90: ...Functions 3 22 Logbook M200D PROFIBUS PROFINET 90 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 118: ...Mounting connection 4 2 Connection M200D PROFIBUS PROFINET 118 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 222: ...Appendix A 2 Order numbers M200D PROFIBUS PROFINET 222 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 224: ...Correction sheet M200D PROFIBUS PROFINET 224 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 232: ...Index M200D PROFIBUS PROFINET 232 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 233: ......