Operating modes and master control function
3.6.1
Operating modes
Control source and location of control
The operating modes assign access rights to the various control sources (access sources). The
control source that possesses the rights for controlling and writing access has control. As only
one control source can ever have control at one time, different priorities are assigned to the
modes. Read access is also possible without control.
6,5,86
:(%
6,5,86
①
Control source: 3RW5 HMI High Feature, operating mode: Manual operation local - HMI controlled
②
Control source: Web server, operating mode: Manual operation bus - web server controlled
(in combination with 3RW5 PROFINET High Feature communication module from firmware ver‐
sion V2.0)
③
Control source: PLC, operating mode: Automatic
④
Control source: Modbus client or Modbus master, operating mode: Automatic
⑤
Control source: SIRIUS Soft Starter ES (TIA Portal) Premium / Professional, operating mode: Man‐
ual operation bus - PC controlled
⑥
Control source: Digital inputs, operating mode: Manual operation local - Input controlled or Au‐
tomatic operation - Input controlled
⑦
Control source: SIRIUS Soft Starter ES (TIA Portal), operating mode: Manual operation local - PC
controlled
"Automatic" mode
For the "Automatic" mode you require a 3RW5 communication module and a higher-level control
(e.g. PLC). The control source is connected to the 3RW55 or 3RW55 Failsafe soft starter via the
3RW5 communication module.
Description
3.6 Operating modes and master control function
SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters
32
Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006