Maintenance and service
9.4 Restoring factory setting
SIRIUS 3RW50 soft starter
190
Manual, 09/2019, A5E35628455002A/RS-AA/001
9.4.2
Restoring the factory settings via High Feature 3RW5 HMI
Requirements
●
Make sure that the motor is switched off and you do not start the motor while restoring the
factory settings.
To ensure the quickest and most fault-free restoration of the factory setting, it is
recommended that you disconnect the main voltage at the 3RW5 soft starter.
●
3RW5 HMI High Feature
Menu: "Parameters > Factory settings"
●
Access protection to 3RW5 HMI High Feature is not active or has been removed.
●
The 3RW5 HMI High-Feature (LOCAL) has master control.
Procedure
1.
Select the desired menu item.
–
Soft starter
–
Communication module
–
HMI High Feature
–
All devices
2.
Confirm the menu item by pressing the OK key.
Result
The factory setting of the selected device or all devices is restored.
Note the effects of the factory settings described in Chapter Effects of the factory setting
(Page 189).
Содержание SIRIUS 3RW50
Страница 8: ...Table of contents SIRIUS 3RW50 soft starter 8 Manual 09 2019 A5E35628455002A RS AA 001 ...
Страница 38: ...Description 1 13 Support Request SIRIUS 3RW50 soft starter 38 Manual 09 2019 A5E35628455002A RS AA 001 ...
Страница 90: ...Connecting 4 11 COM connection cable SIRIUS 3RW50 soft starter 90 Manual 09 2019 A5E35628455002A RS AA 001 ...
Страница 160: ...Functions 7 12 3RW5 HMI High Feature SIRIUS 3RW50 soft starter 160 Manual 09 2019 A5E35628455002A RS AA 001 ...
Страница 184: ...Messages and diagnosis 8 11 Logbooks SIRIUS 3RW50 soft starter 184 Manual 09 2019 A5E35628455002A RS AA 001 ...
Страница 202: ...Circuit diagrams 12 1 CAx data SIRIUS 3RW50 soft starter 202 Manual 09 2019 A5E35628455002A RS AA 001 ...