Error codes (bytes)
Error message
Cause
high
low
80
H
C2
H
Temporary lack of resources in the device
• No free input buffer
• The data set is currently being updated
• The data set request is currently active on another
interface
80
H
C3
H
Resource not available
• Module not available
7.5
Disable or enable group error and group warning
With the parameters "Group error" and "Group warning" you determine whether interrupts (error
interrupts and maintenance interrupts) are transmitted via PROFINET. In the factory setting,
Group error and Group warning are enabled and alarms (error alarms and maintenance alarms)
are transmitted
Setting options
You can disable or enable transmission of error interrupts (group error) and maintenance
interrupts (group warning) via the bus connection in the following ways:
• Configuration software of the controller, e.g. STEP 7
• User program via data set 131 (Page 162)
• SIRIUS Soft Starter ES (TIA Portal) Premium / Professional via 3RW5 communication module
Brief overview: Window "Project Navigation" with current project under created Soft Starter >
"Parameters" >Window "Work area" > "Communication module > Group error / Group
warning"
• SIRIUS Soft Starter ES (TIA Portal) via local interface on the 3RW5 HMI High Feature
Brief overview: See SIRIUS Soft Starter ES (TIA Portal) Premium / Professional
via 3RW5 communication module
• 3RW5 HMI High Feature (Page 80)
Messages and diagnostics
7.5 Disable or enable group error and group warning
SIRIUS 3RW5 PROFINET communication modules
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004
79