Setting options
• 3RW5 HMI High Feature (firmware version V3.1 or higher)
Menu: "Parameter > Communication Module > Web Server" (if web server is activated)
Menu: "Parameter > Communication Module > OPC UA server" (if OPC UA server is activated)
The parameter and setting in both menus are identical.
You will find more information on operating the 3RW5 HMI High Feature in the Equipment
Manual of the 3RW5 soft starter.
• User program via data set 131 (Page 162)
Parameter
Parameter
Description
Operation without PN control
• No (factory setting)
A PLC as control source ("Automatic" mode) is required. If
the 3RW5 soft starter does not detect a bus start, an error
is reported.
• Yes
A PLC as control source ("Automatic" mode) is not possible.
Only connections with SIRIUS Soft Starter ES (TIA Portal)
Premium / Professional, a web server and OPC UA server
are possible via the 3RW5 PROFINET High Feature com‐
munication module.
8.6
System redundancy S2
Requirement
• 3RW5 PROFINET High Feature communication module with firmware V3.0 or higher
System redundancy S2
The PROFINET system redundancy S2 enables the setup of system-redundant plants. The goal of
high availability automation systems is to reduce production downtime.
Reference
You can find more information on the Internet (
https://support.industry.siemens.com/cs/ww/en/
Functions
8.6 System redundancy S2
SIRIUS 3RW5 PROFINET communication modules
136
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004