Technical data
9.7 Overload protection/device protection characteristic
SIRIUS 3RM1 motor starter
Manual, 06/2016, A5E0345285095020A/RS-AE/005
147
Resistive loads
The tripping characteristic shown does not apply for resistive loads at a setting value of 10 A.
In this case, tripping takes place as follows:
Table 9- 1
Tripping for resistive loads at a setting value of 10 A
Tripping after
10 A < load current < 15 A
20 s
Load current > 15 A
1 s